Model# 467
600V
Low Voltage Potential Transformer
- Terminals are 6-32 screws with cupwashers.
- The core and coil assembly is encased in a thermoplastic case and filled with resin.
- These transformers are designed for operation line-to-line. They may also be operated line-to-ground, or line-to neutral, at reduced voltage (58% of rated volts).
- It is desirable to use the proper size fuse in the secondary to protect the P.T. Use a 0.40 Amp fuse with Model 467
- With two exceptions these transformers are ANSI C57.13 group 1. Those marked * are group 2.
Overview
Insulation Class 0.6kV ā 10kV BIL
Thermal Rating40VA at 30Ā°C Amb. ā 27VA at 55Ā°C Amb. (60Hz)
Weight4.0 Lbs
Accuracy
Accuracy ClassĀ±1% at all burdens up to 5VA at 1.0 and 0.95 P.F.
Input
Volts0-69.3V thru 0- 600V
Frequency60Hz
Output
Standard120V
245941
E238872
Need Assistance? Call: 614-889-6152
Not the right part? View all Potential Transformers
Detailed Model Specifications
Click below to see available detailed specifications
While these tables work on mobile devices, they are best viewed on a desktop computer.
Catalog Number | Input Voltage | Output Voltage | Accuracy Class at 5 VA | Thermal Rating 60Htz at 30Ā°C Amb. | Thermal Rating 27VA at 55Ā°C Amb. | Insulation Class | Weight |
---|---|---|---|---|---|---|---|
467-069 | 69.3V | 120V | 0.58:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-120 | 120V | 120V | 1:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-208 | 208V | 120V | 1.73:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-240 | 240V | 120V | 2:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-277 | 277V | 120V | 2.31:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-288 | 288V | 120V | 2.4:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-300 | 300V | 120V | 2.5:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-346 | 346V | 120V | 2.88:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-480 | 480V | 120V | 4:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |
467-600 | 600V | 120V | 5:1 | Ā±1% | 40 VA | 600 V | 4 Lbs |