Model# 450 600V

Low Voltage Potential Transformer

  • The primary and secondary terminals are No. 10-32 screws into 3/8″ deep brass inserts and fitted with one lock washer and one flat washer and are contained in a sealable terminal cover.
  • The core and coil assembly is encased in a thermoplastic shell and filled with resin.
  • These transformers are designed for operation line-to-line. They may also be operated line-to-ground or line-to-neutral, at reduced voltage, (58% of rated volts).
  • It is desirable to use a 8.0 amp BBS type fuse in the secondary to protect the transformer.
  • With two exceptions these transformers are ANSI C57.13 group 1. Those marked * are group 2.
  • This page contains a circle diagram for the estimation of the errors for other than rated burdens.
  • When only one fuse is used, it must be connected into the line side (H1) terminal wiring. This will prevent the presence of voltage at the H1 terminal for a ruptured fuse in the neutral (H2) terminal wiring for line-to-neutral connected transformers.

Overview

Insulation Level(0.6kV) ā€“ (10kV BIL Full Wave)
Thermal Rating750 VA at 30Ā°C amb. ā€“ 500 VA at 55Ā°C amb.
Weight25 Lbs

Accuracy

Accuracy Class0.3 W, X, M, Y and 1.2Z. (**) are 0.3 W, 0.6 X, M, Y

Input

Volts0-69.3V thru 0- 600V
Frequency60Hz

Output

Standard120V

Flex-Core 450 Low Voltage Potential Transformer ā€“ Accurate Voltage Monitoring for Electrical Systems