Current Transformer Secondary Wire Sizing Calculator
Use the calculator below to determine the proper gauge wire for your application.
Current Transformer Burden Rating(VA): | |
Nominal CT Secondary Current(Amps): | |
Wire Length Between CT and Meter(ft): | |
Input burden of Meter(VA): | |
Recommended Wire Size: | |
Maximum CT Rating(Ohms): | |
Metering Rating(Ohms): | |
Maximum Secondary Resistance per Foot(Ohms): |
16AWG | 0.00417 |
14AWG | 0.00263 |
12AWG | 0.00165 |
10AWG | 0.00104 |
8AWG | 0.00065 |
6AWG | 0.00041 |