Model# GW5

Precision AC Watt or VAR Transducer

  • Equipment monitoring for process control.
  • Integration into energy management systems, or a variety of sub-metering applications.
  • Measurement using direct-connection, current transformers, and/or potential transformers.
  • Accurate regardless of variations in voltage, current, power factor, or load.
  • Available with 1, 2, 2 1/2 or 3 element configurations. Provides bi-directional operation. (Except for 4-20mA output models)
  • Accuracy maintained over wide temperature range, calibration traceable to NIST.

Overview

Response Time (99%)<400 ms
Output Loading (Ī©) See Tables
Output Ripple< 0.5% F.S.
Temperature Effect(-20Ā°C to +65Ā°C) Ā±0.005%/Ā°C

Accuracy

ClassĀ± 0.2% RDG Ā±0.04% F.S.

Input

Volts0-150V thru 0-600V/0-5A
Frequency Range58-62Hz
Optional 50Hz48-52Hz

Output

StandardĀ±1mA, Ā±10V, Ā±5V, 4-20mA or 4-12-20mA
Burden Voltage<0.1VA/phase
Burden Current<0.28VA/phase

Model# GW5-watt-transducers

Need Assistance? Call: 614-889-6152

Detailed Model Specifications

Click below to see available detailed specifications

While these tables work on mobile devices, they are best viewed on a desktop computer.